Retrofit Fire Rated Pipe Wraps for Stackwork
|
|
Blazebrake™ fire rated pipe wraps are Retrofit fire and smoke protection devices for Stackwork PVC plastic pipe penetrations through existing or new cored holes in Concrete Floors. Blazebrake™ Pipe Wraps are installed around the pipe then recessed up into the hole until flush with the bottom of the concrete slab.
Suitable for use: - Where small hole clearances exist between the hole and the pipe - Flush to ceiling finish - Where surface mounted retrofit fire collars are not suitable - No tools installation method. - Factory sealed plastic sleeve. |
|
SPECIFICATIONS
|
For technical data relating to applications tested ,fire rating levels and installation diagrams for Concrete floor penetrations refer to Brochure - "Retrofit fire rated devices for cable & pipe services" and Fire test certificates in technical literature section
Part no RFW40R RFW50R RFW65R RFW80R RFW100R
|
Pipe size(nom)/ type
|
PVC 40mm
|
PVC 50mm
|
PVC 65mm
|
PVC 80mm
|
PVC 100mm
|
|
Pipe Diameter approx
|
57mm
|
72mm
|
82mm
|
102mm
|
127mm
|
Intumescent material: Expanding fire resistant .
|
Pipe Wrap Packaging
|
Factory Sealed Plastic Sleeve with adhesive tab
|
|
Pipe Wrap Length
|
To suit pipe circumference
|
|
Pipe Wrap Height
|
50mm (approx )
|
|
|
|
FEATURES & BENEFITS
|
- Up to 3 hour Fire rating in Concrete floors - Tested to and complies with Australian Standard AS1530.4 & AS4072.1 - Flush to ceiling installation - Choice of 5 sizes to suit pipe diameters 40/50/65/80/100mm (nom) - One piece Sealed Wrap in plastic sleeve complete with adhesive tab - Fast and easy installation
Note : Consult tested applications and fire test data before commencing use.Do not cut or tamper with sealed pipe wraps in plastic sleeve.
|
|
|
INSTALLATION GUIDE
|
Important : Consult tested applications & fire test data before commencing use. Do not cut or tamper with sealed wraps.
Concrete Floor Slabs 1. Ensure there is adequate annular space between the pipe & the side of the hole to allow the thickness of the pipe wrap to be placed around the pipe. 2. Wrap the pipe wrap around the circumference of the pipe as tightly as possible ensuring any spaces between the wrap & pipe are minimal. Remove paper covering top of adhesive tab and press tab firmly down onto plastic sleeve to hold wrap closed around the pipe. 3.Slide the wrap into position flush with the underside of the concrete floor. 4.Fill the remaining space between the pipe wrap and the surrounding concrete hole with Blazebrake™ Sealant to appropriate depth. 5.Check that the bottom edge of the wrap is exposed and is visible from underneath the floor.
Note : Refer to Brochure "Retrofit fire rated devices for cable & pipe services" in technical data section for installation instructions with illustrations .

|
|
|